MBC-2XU00AAC definite purpose contactors (2-pole,20A ) are ideal for(HVAC) air conditioning, refrigeration, heating, data processing, welding, elevators, hoists & cranes, lighting, pools & spas and food service equipment.

Product Feature:
1.Unique amortization system to eliminate contact bounce
2.Low cost
3.Accessories modification quickly and easily without using tools
4.Various kinds of terminals for customers' special requirements
5.Easy to change the coil
6.General amounting size, easy for replacement
7.Can be combined with a thermal overload relay to form an electromagnet starter to protect the line in which overload operation may occur
8.Double E magnet assembly providing optimal performance with reduced power consumption
9.Effective dustproof cover available
10.Silver Cadmium Oxide contacts provide long electrical endurance.
11.Class F high temperature insulated coils are standard.

Specifications:

NUMBER
OF
POLES
COIL
VOLTAGE
50/60HZ
FULL
LOAD
AMPS
LINE
VOLTAGE
LOCKED
ROTOR
AMPS
RESISTIVE
SMPS
RATING
MAXIMUM HORSEPOWER BOX
QUANTITY
APPROX
UNIT
WEIGHT
VOLTAGE SINGLE
PHASE
20FLA-2POLE
2 24
120
208/240
277
20 240/277
480
600
 
120
100
80
 
30
30
30
 
120
240

 
2
3

 
50 .27 kg
25FLA-11/2&2POLE
1
with shunt
24
120
208/240
277
25 240/277
480
600
 
150
50
40
 
30
30
30
 
120
240

 
1
2

 
50 .23 kg
2 24
120
208/240
277
25 240/277
480
600
 
150
125
100
 
35
35
35
 
120
240

 
2
3

 
50 .27 kg
30FLA-11/2&2POLE
1
with shunt
24
120
208/240
277
30 240/277
480
600
 
150
75
50
 
40
40
40
 
120
240

 
1
2

 
50 .23 kg
2 24
120
208/240
277
30 240/277
480
600
 
150
125
100
 
40
40
40
 

120
240

 

2
3

 
50 .27 kg
40FLA-11/2&2POLE
1
with shunt
24
120
208/240
277
40 240/277
480
600
 
240
200
160
 
50
50
50
 
120
240

 
2
3

 
50 .23 kg
2 24
120
208/240
277
40 240/277
480
600
 
240
200
160
 
50
50
50
 
120
240

 
2
3

 
50 .27 kg

OTHER SPECIFCATIONS 20-35 FLA 40 FLA
Line and Load Terminals #10-32Screw* BoxLugs*
Wire Size Awg Min-Max 16-8* 14-4Cu/Al
Tightening Torque(recommended) 25in.Ibs 40 in.Ibs
Coil Termination Dual.250 QC(2) Dual.250 QC(2)
Quick Connects.250 std.-1 or 11-2 Pole Quad Quad
Quick Connects.250 std.-2 Pole Dual or Quad Dual or Quad
Covers Optional Standard
Insulation System 130 Class B 130 Class B
*stranding must be split for #8 wire*Permissible Ambient Temperature: -40/65 -40F/150F

COIL TECHNICAL DATA 50/60hz 1POLE CONTACTORS 2POLE CONTACTORS
Nominal Coil Voltage 24 120 208/240 277 24 120 208/240 277
Maximum Pickup Volts 18 88 177 221 18 88 177 221
Drop-Out Volts Range 6-15 20-70 40-140 50-165 6-15 20-70 40-140 50-160
Nominal Inrush VA@50Hz 31 31 35 31 22 22 22 22
Nominal Inrush VA@60Hz 28 28 32 28 20 20 20 20
Nominal Sealed VA@50Hz 6 6 7 6 5.5 5.5 5.5 5.5
Nominal Sealed VA@60Hz 5 5 6 5 4.5 4.5 4.5 4.5
Nominal DC Resistance-Ohms 17.5 450 1800 2252 13 275 1056 1772